- Formula
- Total(band) = Σ element attenuations (Straight duct, Bend, Junction/Split, End reflection, Flexible duct)
- Output
- dB (negative = attenuation) — one row per element plus the total, per band
- Bands
- 31.5 Hz – 8 kHz row; no element fills 31.5 Hz, and the total is blank at any band an element does not cover
- Standard / Source
- CIBSE Guide B4
- Access
- Toolbar block
What it does
Chains the duct-borne losses of a run into one block: a sequence of Straight duct, Bend, Junction/Split, End reflection and Flexible duct elements, each with its own yellow inputs and its own attenuation row, and a final Duct Run Total row with the band-by-band sum.
Choosing Mechanical › Ducting › Duct run… opens the Duct run tile. Click an element card to start a new run at the selected cell, or — with the selection inside an existing run — to append that element to it. Elements are removed with the ✕ beside them in the tile. The run is available on 1/1-octave sheets only.
Each new element is filled in from the run so far, so a run is usually entered once and then only edited where it changes:
- Shape and size follow the element immediately before it. A junction passes on its followed branch, a bend its width (as the diameter of a round bend, or the width of a square or radiused one), and a flexible duct its diameter. A round bend gives a circular section; a square or radiused bend gives a rectangular one. A size the previous element does not have (e.g. the height after a square bend) comes from the nearest earlier section of the same shape, otherwise the element's own default.
- Method (CIBSE or ASHRAE) follows the nearest earlier element that offers the same choice; a round bend is skipped, because a bend seeded round always uses CIBSE Table 4.24 (ASHRAE has no round elbow). Without one, CIBSE.
- A new junction's other branch keeps its own default size (Ø400 mm, or 415 × 375 mm); edit it to the branch you are not following.
- An ASHRAE end reflection takes an effective diameter: the previous diameter, or D = √(4wh/π) for a rectangle, rounded to the millimetre.
- A flexible duct takes the previous diameter only if it is one of ASHRAE Table 25's sizes (100–400 mm); otherwise it starts at 200 mm.
- A run started on an empty selection starts rectangular (straight duct 300 × 300 mm).
Equation
Each is calculated exactly as the standalone calc of the same kind: Straight Duct Attenuation, Duct Bend Attenuation, Junction/Split, End Reflection Loss and Lined Flexible Duct.
ℹ️ No silent partial totals. The total is written at a band only when every element has a value there. If one element's method does not cover a band (e.g. a flexible duct has no 8 kHz value, and no element has a 31.5 Hz value), that element's own row is blank there and so is the total. An element with invalid inputs leaves the total blank at every band.
Inputs
The block has no inputs of its own — each element's rows carry the inputs of the calc it borrows from:
| Element | Inputs | Same as |
|---|---|---|
| Straight duct | Method (CIBSE/ASHRAE), duct type, size, length (default 1 m), lining | Straight Duct Attenuation |
| Bend | Method (CIBSE/ASHRAE), shape (square/round/radiused), width, turning vanes, lining, number of bends | Duct Bend Attenuation |
| Junction/Split | duct type, followed and not-followed branch sizes | Junction/Split |
| End reflection | Method (CIBSE/ASHRAE), diffuser type, size (ASHRAE: effective diameter) | End Reflection Loss |
| Flexible duct | diameter (ASHRAE Table 25 sizes), length | Lined Flexible Duct |
Worked example
A new run: Straight duct (CIBSE, rectangular 300 × 300 mm as it starts, unlined, length edited to 5 m), then a Bend (square, width 300 mm and CIBSE carried over, no vanes, unlined), then an End reflection (CIBSE grille/swirl, rectangular 300 × 300 mm carried over — the width from the bend, the height from the straight duct):
| Band (Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 |
|---|---|---|---|---|---|---|---|---|
| Straight duct (dB) | −10 | −7 | −3 | −3 | −3 | −3 | −3 | −3 |
| Bend (dB) | 0 | 0 | −1 | −5 | −8 | −4 | −3 | −3 |
| End reflection (dB) | −11.8 | −6.9 | −3.1 | −1.1 | −0.3 | 0 | 0 | 0 |
| Duct Run Total (dB) | −21.8 | −13.9 | −7.1 | −9.1 | −11.3 | −7 | −6 | −6 |
(The straight duct uses CIBSE Table 4.19 for an unlined rectangular duct over 5 m; the bend uses Table 4.22. The 31.5 Hz cell of the total is blank, because no element defines that band. Change the straight duct's method to ASHRAE and a bend or end reflection added after it starts as ASHRAE too.)
Source
Each element cites its own source: CIBSE Guide B4 Tables 4.19/4.20 or ASHRAE 2023 (straight duct; SRL survives only in blocks saved before it was withdrawn), CIBSE Guide B4 Tables 4.22–4.24 or ASHRAE 2023 (bend), CIBSE Guide B4 Formula 4.5 = ASHRAE 2023 Table 26 (junction), CIBSE Guide B4 (2016) or ASHRAE 2023 (end reflection), and ASHRAE 2023 Table 25 (flexible duct). The total is a plain band-wise sum.