- Formula
- CIBSE: ∆Lr = −10·log₁₀[1+(0.8λ/πd)^1.88] (grille/swirl) or ERL = −10·log₁₀(1/T) (slot); ASHRAE: ERL = −10·log₁₀[1+(a₁·c₀/πfD)^a₂]
- Output
- dB (negative = attenuation)
- Bands
- 63 Hz – 8 kHz (0 dB at ≥2 kHz on CIBSE grille/swirl; flat on slot)
- Standard / Source
- CIBSE Guide B4
- Access
- Toolbar block
What it does
Gives the end reflection loss at a duct termination (e.g. a grille discharging into a room). Where a duct opens abruptly into a much larger space, low-frequency energy is partly reflected back down the duct instead of radiating out — an effective low-frequency attenuation that fades to nothing at high frequency.
A Method switch chooses the model:
- CIBSE — Guide B4 (2016), flush termination. A Diffuser type toggle further splits this into grille/swirl (diameter-based) or slot (area-ratio-based).
- ASHRAE — the 2023 ASHRAE Handbook relation, for blade, grille or slot diffusers (slot again uses the area-ratio form).
Equation
CIBSE, grille/swirl:
Rectangular terminations use an equivalent diameter . The loss is taken as 0 dB at 2 kHz and above.
CIBSE or ASHRAE, slot:
Frequency-flat — the same value at every band.
ASHRAE, blade/grille:
with a₁ = 0.7 (ducted termination), a₂ = 2, c₀ = 343 m/s. Capped at −14 dB.
Inputs
| Input | Meaning | Unit | Method / type |
|---|---|---|---|
| Method | CIBSE or ASHRAE | select | both |
| Diffuser type | grille-swirl or slot (CIBSE); blade, grille or slot (ASHRAE) | select | both |
| Duct type, Diameter / Width×Height | duct or grille cross-section | mm | CIBSE, grille-swirl |
| S1, S2 | upstream duct area, diffuser outlet area (defaults 0.036 / 0.0061 m² on CIBSE, 0.045 / 0.0056 m² on ASHRAE) | m² | slot (either method) |
| Effective duct diameter | D | m | ASHRAE, blade/grille |
ℹ️ New blocks and switching. A new block starts CIBSE, grille/swirl, rectangular 450 × 300 mm. When you switch Diffuser type or Method and back, the rows that disappeared come back with the values they held: a rectangular 600 × 400 mm termination switched to slot and back is rectangular 600 × 400 mm again. Where a size has never been entered, it is carried over from the one you have: a circular Diameter takes the width; ASHRAE's effective diameter takes the CIBSE diameter, or √(4wh/π) for a rectangle, to the millimetre; a CIBSE Diameter revealed from ASHRAE takes D. A block saved without a Duct type row reads as circular, exactly as before. Each switch is a single undo step.
Worked example — CIBSE, grille/swirl
Circular Ø450 mm termination:
| Band (Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 |
|---|---|---|---|---|---|---|---|---|
| ΔLr (dB) | −9.68 | −5.17 | −2.10 | −0.68 | −0.19 | 0 | 0 | 0 |
The effect is strongly low-frequency: nearly 10 dB at 63 Hz, negligible by 1 kHz.
Worked example — CIBSE or ASHRAE, slot
S1 = 0.036 m², S2 = 0.0061 m²:
T = 4(0.036)(0.0061)/(0.0421)² = 0.496 → ERL = −10·log₁₀(1/0.496) = −3.05 dB, applied equally across every band.
Worked example — ASHRAE, blade
Blade diffuser, D = 0.276 m, ducted (a₁ = 0.7):
| Band (Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 |
|---|---|---|---|---|---|---|---|---|
| ERL (dB) | −13.08 | −7.71 | −3.48 | −1.16 | −0.32 | −0.08 | −0.02 | −0.01 |
Source
CIBSE Guide B4 (2016) — end reflection loss, no loss assumed at 2000 Hz and above (grille/swirl); slot diffuser relation. ASHRAE, 2023 ASHRAE Handbook — HVAC Applications, Chapter 49 (Sound and Vibration Control) — end reflection loss relation (blade/grille) and slot diffuser relation.