- Formula
- dL = 10·log₁₀(A₁/(A₁+A₂)) (CIBSE Guide B4 Formula 4.5 = ASHRAE 2023 Table 26)
- Output
- dB (negative = attenuation), same value in every band from 63 Hz
- Bands
- 63 Hz – 8 kHz (the straight duct's octave bands; same value in every band)
- Standard / Source
- CIBSE Guide B4
- Access
- Toolbar block
What it does
Gives the attenuation a duct-borne sound level suffers at a branch (T-)junction, per CIBSE Guide B4 (2016) Formula 4.5 — the loss on the branch you follow, from splitting into a branch you don't. ASHRAE 2023 Table 26 (duct branch sound power division) is the same formula, so there is one calc with no method choice. The result is the same in every band; like every other duct element it is written from 63 Hz to 8 kHz (31.5 Hz is left blank). On a 1/3-octave sheet it fills only the eight octave-centre bands (63 Hz … 8 kHz), and on the low-frequency sheet only 63, 125 and 250 Hz — the same bands as the straight duct.
Equation
A₁ = cross-sectional area of the branch followed, A₂ = cross-sectional area of the branch not followed. For ASHRAE's form, where the sound divides between the followed branch and several others, enter the other branches as one equivalent not-followed branch with their total area (e.g. 400 mm and 300 mm round branches = one 500 mm branch, since 400² + 300² = 500²). ASHRAE prints the result rounded to whole dB.
ℹ️ A circular branch's area is the ordinary circle area π·(d/2)² (d in metres); rectangular branches use width × height. (dL is an area ratio, so the pre-2026-10-07 π·d² convention never changed this result.)
Inputs
| Input | Meaning | Unit | Example |
|---|---|---|---|
| Duct type | circular or rectangular, applies to both branches (a new block starts rectangular) | select | circular |
| Followed diameter / width×height | cross-section of the branch followed | mm | 250 (circular) |
| Not-followed diameter / width×height | cross-section of the branch not followed | mm | 400 (circular) |
Worked example
Circular branches, followed d₁ = 250 mm, not-followed d₂ = 400 mm:
A₁ = π·(0.125)² = 0.0491 m², A₂ = π·(0.2)² = 0.1257 m²
dL = 10·log₁₀(0.0491 / 0.1748) = −5.51 dB, applied identically across the bands 63 Hz – 8 kHz.
Source
CIBSE Guide B4 (2016), Formula 4.5 — attenuation of the followed branch at a duct junction; ASHRAE 2023 Handbook — HVAC Applications (SI), Chapter 49, Table 26 (duct branch sound power division), the same relation. In a Duct run the followed branch takes the shape and size of the element before it; the not-followed branch keeps its own.