What it does
Gives the insertion loss of a lined (non-metallic, insulated) flexible duct, read from ASHRAE 2023 Handbook — HVAC Applications, Chapter 49, Table 25, by its nominal diameter and length. It is also available as an element of a Duct run.
Equation
Timbral writes the loss negative (an attenuation), like every other duct element.
ℹ️ Table lookup. Table 25 lists ten nominal diameters (100, 125, 150, 175, 200, 225, 250, 300, 350 and 400 mm) and four lengths (0.9, 1.8, 2.7 and 3.7 m). Any other diameter gives N/A: Timbral does not interpolate between sizes. For the length, Timbral reads a tabulated length directly, interpolates linearly between two tabulated lengths, scales the 0.9 m row by L/0.9 below 0.9 m, and holds the 3.7 m row above 3.7 m (no extrapolation). The 63 Hz column is ASHRAE's own estimate. Table 25 has no 8 kHz column, so 8 kHz is blank (and a duct run containing one has a blank 8 kHz total).
Inputs
| Input | Meaning | Unit | Example |
|---|---|---|---|
| Flexible duct diameter | one of Table 25's ten nominal diameters | mm | 200 |
| Flexible duct length | length of the flexible duct (must be greater than 0) | m | 2.0 |
Worked example
D = 200 mm, L = 2.0 m, between the 1.8 m and 2.7 m rows (fraction (2.0 − 1.8)/(2.7 − 1.8) = 0.222):
| Band (Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 |
|---|---|---|---|---|---|---|---|
| Table 25, 1.8 m (dB) | 4 | 6 | 11 | 17 | 19 | 19 | 12 |
| Table 25, 2.7 m (dB) | 6 | 8 | 16 | 25 | 28 | 28 | 18 |
| Result (dB) | −4.4 | −6.4 | −12.1 | −18.8 | −21.0 | −21.0 | −13.3 |
(e.g. at 500 Hz: 17 + 0.222 × (25 − 17) = 18.8, written as −18.8 dB.)
Source
ASHRAE 2023 Handbook — HVAC Applications (SI), Chapter 49, Table 25 (insertion loss of lined flexible duct). Bands 63–4000 Hz.