- Formula
- L₂ = L₁ + SRI + 10·log₁₀(S / A)
- Output
- dB — two rows per band: Transfer Function (level difference) and Predicted receiving-room SPL
- Bands
- Follows the input spectrum
- Standard / Source
- General acoustics (no standard cited)
- Access
- Toolbar block
What it does
Predicts the sound pressure level in a receiving room next to a source room, through a separating partition of area S and sound reduction index SRI, where the receiving room has total absorption A. Flanking transmission is not included — this is the direct-path estimate only. Ribbon: Buildings → Room → Room.
The block has two result rows: the Transfer Function (SRI + 10·log₁₀(S/A), which needs no source level) and, below it, the Predicted SPL in the receiving room. The source-room SPL is optional — leave it blank and only the Transfer Function is filled.
Equation
The SRI is entered as a negative value. The receiving-room absorption A is derived band by band from the room's volume and reverberation time, A = 0.161·V / T₆₀ (a band whose T₆₀ is blank or zero is left blank). Typing A directly is no longer offered; blocks saved with that option still recalculate.
Inputs
| Input | Meaning | Unit | Example |
|---|---|---|---|
| L₁ | source-room SPL (a spectrum row; optional) | dB | 85 |
| SRI | partition sound reduction index (negative) | dB | −20 |
| S | partition area | m² | 20 |
| V | receiving-room volume | m³ | 35 |
| T₆₀ | receiving-room reverberation time (a spectrum row) | s | 0.75 |
Worked example
At 63 Hz — source level 85 dB, partition SRI = −20 dB, S = 20 m², receiving room V = 35 m³ with T₆₀ = 0.75 s, so A = 0.161 × 35 / 0.75 = 7.51 m²:
The Transfer Function row reads −20 + 4.25 = −15.7 dB at the same band.
Source
Standard direct-path room-to-room relation (excludes flanking). No specific published standard is cited in the software.