- Formula
- Lw,out = Lw,in − TL + 10·log₁₀(L) − E (CIBSE Guide B4 Formula 4.9, Table 4.30, Figure 4.42)
- Output
- dB — sound power level radiated by the duct walls (Lw) per band
- Bands
- 63 Hz – 4 kHz
- Standard / Source
- CIBSE Guide B4
- Access
- Toolbar block
What it does
Estimates the sound power that breaks out through the walls of a rectangular sheet-steel duct as it passes through a room or ceiling void (the "critical area"), per CIBSE Guide B4 Formula 4.9. Takes the in-duct sound power where the duct enters that area, the steel thickness, the duct section and the exposed length.
Equation
- TL — breakout transmission loss from CIBSE Table 4.30, by steel thickness and cross-section.
- E — the additional duct length effect, which stops a long, low-TL duct from radiating more power than it carries. Timbral interpolates it from CIBSE Guide B4 Figure 4.42.
ℹ️ Table lookup. Table 4.30 lists eleven sections (150×150 to 1200×1800 mm). Timbral uses the nearest one, by the summed difference of the two sides in either order; a tie takes the lower TL band by band (the conservative choice, more breakout), and a larger duct takes the largest section.
Inputs
| Input | Meaning | Unit | Example |
|---|---|---|---|
| Lw,in | in-duct sound power where the duct enters the critical area (a spectrum row) | dB | see below |
| Steel duct thickness | 0.7 (22 swg), 0.9 (20 swg), 1.2 (18 swg) or 1.6 (16 swg) | mm | 0.7 (22 swg) |
| Width, Height | duct cross-section (must be greater than 0) | mm | 300 × 300 |
| L | exposed duct length inside the critical area | m | 5 |
Worked example
0.7 mm (22 swg) steel, 300 × 300 mm, L = 5 m (10·log₁₀L = 6.99 dB):
| Band (Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 |
|---|---|---|---|---|---|---|---|
| Lw,in (dB) | 80 | 78 | 74 | 70 | 65 | 60 | 55 |
| TL (dB) | 13 | 18 | 19 | 20 | 23 | 26 | 30 |
| E (dB) | 0.60 | 0.35 | 0.32 | 0.30 | 0.25 | 0.21 | 0.17 |
| Lw,out (dB) | 73.4 | 66.6 | 61.7 | 56.7 | 48.7 | 40.8 | 31.8 |
(e.g. at 63 Hz: 80 − 13 + 6.99 − 0.60 = 73.4 dB.)
Source
CIBSE Guide B4 (2016) — Formula 4.9 (duct breakout), Table 4.30 (breakout transmission loss of rectangular ducts) and Figure 4.42 (additional duct length effect). Bands 63–4000 Hz.