Outlet to receiver (Internal)

Formula
Small room: L = Lw + A(V,band) − B(r); Medium room: L = Lw − C(r,band) − 5; Large room (Lprev): L = Lw + 10·log₁₀[Q/(4πr²) + 4/Rc]; Distributed: L = Lw − D(H,S,band)
Output
dB — SPL at receiver, per band
Bands
63 Hz – 4 kHz
Standard / Source
CIBSE Guide B4
Access
Toolbar block

What it does

Predicts the sound pressure level at a receiver point in a room served by a duct outlet or diffuser, from the outlet's sound power. The equation used adapts automatically: a small single room (≤ 430 m³) uses CIBSE Eq 4.20, a medium single room (> 430 m³ and < 4,500 m³) uses CIBSE Eq 4.21, a large/highly reverberant single room (≥ 4,500 m³) falls back to the classic direct-plus-reverberant-field relationship (the same equation used by the standalone "SPL in Room" calc) rather than CIBSE's medium-room table, and a distributed array of ceiling diffusers instead looks up an attenuation from CIBSE Table 4.42 based on floor-to-ceiling height and floor area per diffuser.

Equation

Small room (V ≤ 430 m³), CIBSE Eq 4.20:

L=Lw+A(V,band)−B(r)L = L_w + A(V,\text{band}) - B(r)

Medium room (430 m³ < V < 4,500 m³), CIBSE Eq 4.21:

L=Lw−C(r,band)−5L = L_w - C(r,\text{band}) - 5

Large room (V ≥ 4,500 m³), classic direct + reverberant field:

L=Lw+10log⁡10 ⁣(Q4πr2+4Rc)L = L_w + 10\log_{10}\!\left(\frac{Q}{4\pi r^2} + \frac{4}{R_c}\right)

where Q is the outlet's directivity factor and Rc is the room constant of the large reverberant space — the same relationship the "SPL in Room (Direct + Reverberant)" and "Room Constant" calcs use, applied here per band. Unlike the CIBSE eq 4.20/4.21 tables, this branch is not itself drawn from CIBSE Guide B4 — it's the general-acoustics direct+reverberant relationship, reused because CIBSE's own medium-room table (Eq 4.21 / the C-table) doesn't extend usefully to very large or highly reverberant spaces.

Distributed diffuser array, CIBSE Table 4.42:

L=Lw−D(H,S,band)L = L_w - D(H, S, \text{band})

where A, B, C, D are all read from CIBSE's tabulated room-volume / distance / geometry data. A, B and C are interpolated between table rows and then rounded to the nearest 1 dB before being combined with Lw; D is read from the matching Table 4.42 height/area band (no interpolation — a height or area outside the table gives no result).

Inputs

InputMeaningUnitExample
Lwoutlet sound power (a spectrum row)dBsee below
Layoutsingle outlet or distributed array (select)—Single outlet
Vroom volume (single outlet only)m³300
rdistance from outlet (single outlet only)m1.5
H, Sceiling height, floor area per diffuser (distributed array only)m, m²2.5, 20
Qoutlet directivity factor (large room only)—Hemispherical (Q=2)
Rcroom constant of the large space (large room only)m²500

Worked example

Single outlet, V = 300 m³ (≤ 430 m³ → Eq 4.20), r = 1.5 m (A = 0, −1, −2, −3, −4, −5, −6 dB after rounding; B = 7 dB):

Band (Hz)63125250500100020004000
Lw (dB)80787470656055
L (dB)73.070.065.060.054.048.042.0

Single outlet, V = 5,000 m³ (≥ 4,500 m³ → large-room Lprev), r = 6 m, Q = 2 (Hemispherical, default), Rc = 500 m² (default). The correction 10·log₁₀[Q/(4πr²) + 4/Rc] = −19.06 dB is the same at every band:

Band (Hz)63125250500100020004000
Lw (dB)80787470656055
L (dB)60.958.954.950.945.940.935.9

Source

CIBSE Guide B4, Noise and Vibration Control — Equations 4.20 and 4.21, and Table 4.42. The large-room branch is not itself a CIBSE citation — see the note under Equation above; it reuses the general direct+reverberant-field relationship.