- Formula
- Small room: L = Lw + A(V,band) − B(r); Medium room: L = Lw − C(r,band) − 5; Large room (Lprev): L = Lw + 10·log₁₀[Q/(4πr²) + 4/Rc]; Distributed: L = Lw − D(H,S,band)
- Output
- dB — SPL at receiver, per band
- Bands
- 63 Hz – 4 kHz
- Standard / Source
- CIBSE Guide B4
- Access
- Toolbar block
What it does
Predicts the sound pressure level at a receiver point in a room served by a duct outlet or diffuser, from the outlet's sound power. The equation used adapts automatically: a small single room (≤ 430 m³) uses CIBSE Eq 4.20, a medium single room (> 430 m³ and < 4,500 m³) uses CIBSE Eq 4.21, a large/highly reverberant single room (≥ 4,500 m³) falls back to the classic direct-plus-reverberant-field relationship (the same equation used by the standalone "SPL in Room" calc) rather than CIBSE's medium-room table, and a distributed array of ceiling diffusers instead looks up an attenuation from CIBSE Table 4.42 based on floor-to-ceiling height and floor area per diffuser.
Equation
Small room (V ≤ 430 m³), CIBSE Eq 4.20:
Medium room (430 m³ < V < 4,500 m³), CIBSE Eq 4.21:
Large room (V ≥ 4,500 m³), classic direct + reverberant field:
where Q is the outlet's directivity factor and Rc is the room constant of the large reverberant space — the same relationship the "SPL in Room (Direct + Reverberant)" and "Room Constant" calcs use, applied here per band. Unlike the CIBSE eq 4.20/4.21 tables, this branch is not itself drawn from CIBSE Guide B4 — it's the general-acoustics direct+reverberant relationship, reused because CIBSE's own medium-room table (Eq 4.21 / the C-table) doesn't extend usefully to very large or highly reverberant spaces.
Distributed diffuser array, CIBSE Table 4.42:
where A, B, C, D are all read from CIBSE's tabulated room-volume / distance / geometry data. A, B and C are interpolated between table rows and then rounded to the nearest 1 dB before being combined with Lw; D is read from the matching Table 4.42 height/area band (no interpolation — a height or area outside the table gives no result).
Inputs
| Input | Meaning | Unit | Example |
|---|---|---|---|
| Lw | outlet sound power (a spectrum row) | dB | see below |
| Layout | single outlet or distributed array (select) | — | Single outlet |
| V | room volume (single outlet only) | m³ | 300 |
| r | distance from outlet (single outlet only) | m | 1.5 |
| H, S | ceiling height, floor area per diffuser (distributed array only) | m, m² | 2.5, 20 |
| Q | outlet directivity factor (large room only) | — | Hemispherical (Q=2) |
| Rc | room constant of the large space (large room only) | m² | 500 |
Worked example
Single outlet, V = 300 m³ (≤ 430 m³ → Eq 4.20), r = 1.5 m (A = 0, −1, −2, −3, −4, −5, −6 dB after rounding; B = 7 dB):
| Band (Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 |
|---|---|---|---|---|---|---|---|
| Lw (dB) | 80 | 78 | 74 | 70 | 65 | 60 | 55 |
| L (dB) | 73.0 | 70.0 | 65.0 | 60.0 | 54.0 | 48.0 | 42.0 |
Single outlet, V = 5,000 m³ (≥ 4,500 m³ → large-room Lprev), r = 6 m, Q = 2 (Hemispherical, default), Rc = 500 m² (default). The correction 10·log₁₀[Q/(4πr²) + 4/Rc] = −19.06 dB is the same at every band:
| Band (Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 |
|---|---|---|---|---|---|---|---|
| Lw (dB) | 80 | 78 | 74 | 70 | 65 | 60 | 55 |
| L (dB) | 60.9 | 58.9 | 54.9 | 50.9 | 45.9 | 40.9 | 35.9 |
Source
CIBSE Guide B4, Noise and Vibration Control — Equations 4.20 and 4.21, and Table 4.42. The large-room branch is not itself a CIBSE citation — see the note under Equation above; it reuses the general direct+reverberant-field relationship.