- Formula
- CIBSE Guide B4 Table 4.43 — DI by mounting & outlet area
- Output
- dB — directivity index (≤ 9 dB)
- Bands
- 125 Hz – 8 kHz
- Standard / Source
- CIBSE Guide B4
- Access
- Toolbar block
What it does
Gives the directivity index (DI) of an outlet indoors — how much the radiated level is raised in the forward direction by the way the outlet is mounted and its size. The DI is read from CIBSE Guide B4 Table 4.43 by mounting position and outlet area — no interpolation: the row with the greatest tabulated area not exceeding S is used (areas beyond the table clamp to its first/last row; position C is 9 dB for any area) — and capped at 9 dB.
Inputs
| Input | Meaning | Unit | Example |
|---|---|---|---|
| Mounting position | the dropdown spells out all three: A — flush with ceiling, B — corner of ceiling and 1 wall, C — corner of ceiling and 2 walls | select | A |
| Outlet area S | free area of the outlet | m² | 0.1 |
Worked example
Mounting A (flush), S = 0.1 m²:
| Band (Hz) | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 |
|---|---|---|---|---|---|---|---|
| DI (dB) | 4 | 6 | 7 | 8 | 9 | 9 | 9 |
Source
CIBSE Guide B4, Table 4.43 — directivity index by mounting position, outlet area and octave band. Bands 125–8000 Hz.