- Formula
- CIBSE Guide B4 Tables 4.43 + 4.44 — angle-dependent
- Output
- dB — directivity correction (floored at −30 dB)
- Bands
- 125 Hz – 8 kHz
- Standard / Source
- CIBSE Guide B4
- Access
- Toolbar block
What it does
Gives the angle-dependent directivity of an outdoor louvre. It takes the position-A directivity index from Table 4.43 and applies an angle correction from Table 4.44 for the receiver's bearing off the louvre axis, interpolated by angle and floored at −30 dB. At 0° (straight ahead) it equals the indoor position-A value; off-axis it falls away sharply.
Inputs
| Input | Meaning | Unit | Example |
|---|---|---|---|
| Outlet area S | free area of the outlet | m² | 0.1 |
| Angle θ | bearing off the louvre axis | ° | 0 |
Worked example
S = 0.1 m², angle 0° (on-axis) — equals the indoor position-A result:
| Band (Hz) | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 |
|---|---|---|---|---|---|---|---|
| DI (dB) | 4 | 6 | 7 | 8 | 9 | 9 | 9 |
At a large off-axis angle the corrections become strongly negative (down to the −30 dB floor).
Source
CIBSE Guide B4, Tables 4.43 + 4.44 — position-A directivity index plus angle correction. Bands 125–8000 Hz.