Fan Sound Power Level

Formula
SRL: Lw = 10·log₁₀(Q) + 20·log₁₀(P) + 40 + correction; CIBSE: Lw = Lws + 10·log₁₀(Q) + 20·log₁₀(P) + 40 + BFI + C
Output
dB — sound power level (Lw) per band
Bands
63 Hz – 4 kHz
Standard / Source
CIBSE Guide B4
Access
Toolbar block

What it does

Estimates a fan's sound power level spectrum from its duty (flow and static pressure). A Method switch chooses between two independent models:

  • SRL — the simpler of the two: a base level from Q and P, shaped by a per-band spectrum correction characteristic of the fan type (forward/backward-curved centrifugal, axial, mixed-flow).
  • CIBSE — CIBSE Guide B4 (2016) Formula 4.1, a more detailed method: the same base level, plus a per-band spectrum correction (and blade-frequency increment) from Table 4.1 for the fan type and wheel size, plus an operating-duty correction from Table 4.3 for how far off its peak-efficiency point the fan runs.

Switching Method changes which inputs the block asks for.

Equation

SRL:

Lw=10 log⁡10(Q)+20 log⁡10(P)+40+correction(band, fan type)L_w = 10\,\log_{10}(Q) + 20\,\log_{10}(P) + 40 + \text{correction}(\text{band, fan type})

CIBSE:

Lw(band)=Lws(type, size, band)+10log⁡10(Q)+20log⁡10(P)+40+BFI+CL_w(\text{band}) = L_{ws}(\text{type, size, band}) + 10\log_{10}(Q) + 20\log_{10}(P) + 40 + \text{BFI} + C
  • Lws — Table 4.1 spectrum correction for the fan type (and, for some types, wheel-size bucket).
  • BFI — the Table 4.1 blade-frequency increment, added only to the single octave band that contains the blade-passage frequency BPF = (rpm/60) × blade count.
  • C — Table 4.3 operating-duty correction, from the fan's off-peak static efficiency: 90–100% → 0 dB, 85–89% → 3, 75–84% → 6, 65–74% → 9, 55–64% → 12, 50–54% → 15 (below 50%, Table 4.3 is undefined and no correction is applied).

ℹ️ Wheel size only matters for some fan types. Table 4.1 splits by wheel size for "Centrifugal: aerofoil/backward curved" (>900 mm vs ≤900 mm), "Pressure blower" (<500 mm vs ≥500 mm), and "Vaneaxial"/"Tubeaxial" (>1000 mm vs ≤1000 mm). "Centrifugal: forward curved", "Centrifugal: radial blade" and "Propeller (cooling tower)" use one row regardless of the wheel-size value entered.

Inputs

InputMeaningUnitMethod
MethodSRL or CIBSEselectboth
Qvolume flow ratem³/sboth
Pfan static pressureN/m²both
Fan typeforward/backward-curved, axial, mixedselectSRL
Fan typeone of the 7 CIBSE Table 4.1 typesselectCIBSE
Wheel sizefan wheel diameter (selects Table 4.1 size bucket where applicable)mmCIBSE
Operating dutyoff-peak static efficiency (selects C from Table 4.3)%CIBSE
Fan speedrpmrpmCIBSE
Bladesnumber of impeller blades—CIBSE

Worked example — SRL

Q = 2 m³/s, P = 500 N/m², forward-curved centrifugal: the block writes Lw in each band from 63 Hz to 4 kHz — the base level from Q and P plus the forward-curved spectrum correction, which Timbral reads from SRL Figure 7.6.

ℹ️ The SRL source data only spans 63 Hz–4 kHz, so no 31.5 Hz or 8 kHz value is produced.

Worked example — CIBSE

Q = 2 m³/s, P = 500 N/m² (base Lw = 96.99 dB), Centrifugal: forward curved, 900 rpm, 12 blades (BPF = 180 Hz → falls in the 250 Hz band, BFI = +2 dB there), 90% operating duty (C = 0 dB):

Band (Hz)63125250500100020004000
Lw (dB)88.9984.9984.9974.9969.9966.9964.99

(250 Hz would otherwise be 82.99 dB before the +2 dB BFI is added, landing it level with 125 Hz.)

Source

SRL, Noise Control in Building Services — fan sound-power data (Figure 7.6), or CIBSE Guide B4 (2016), Formula 4.1 — fan sound power level, with spectrum corrections and blade-frequency increment from Table 4.1 and operating-duty correction from Table 4.3. Both cover 63–4000 Hz.