- Formula
- Direct: Lw = Lp,direct + 10·log₁₀(Ad). Reverberant: Lw = Lp,reverb + 10·log₁₀(Ad) − 6. Combined logarithmically where both are present.
- Output
- dB — sound power level entering the duct (Lw) per band
- Bands
- Follows the input spectrum
- Standard / Source
- CIBSE Guide B4
- Access
- Toolbar block
What it does
Estimates the sound power entering a duct opening (e.g. a return-air grille) from a source's sound field in the room, per CIBSE Guide B4 (2016) Formulas 4.29/4.30. This is the "crosstalk" path by which noise from one room can travel through ductwork into another.
The Direct and Reverberant SPL rows are both optional — pick either one, or both. When both are given, the two contributions are logarithmically (energy) combined per band into a single result; the calc's summary line always shows which path(s) are in use.
Equation
Direct (line-of-sight sound field):
Reverberant (the room's reverberant field — the extra −6 dB accounts for its different relationship between pressure and the power reaching the opening):
Combined, where both paths are supplied:
where Ad is the duct's cross-sectional area.
ℹ️ Circular duct area is the ordinary circle area Ad = π·(d/2)² (d in metres); rectangular is width × height. (Before 2026-10-07 a circular duct used π·d², which put circular-duct crosstalk 6.02 dB high; that was corrected together with the reference spreadsheet.)
Inputs
| Input | Meaning | Unit | Example |
|---|---|---|---|
| Duct type | circular or rectangular | select | rectangular |
| Width, Height (rectangular) / Diameter (circular) | duct cross-section (must be greater than 0 — a blank or 0 size leaves the result blank) | mm | 315 × 210 (circular default 425) |
| Lp,direct | direct-field SPL spectrum in the room (a spectrum row) — optional | dB | see below |
| Lp,reverb | reverberant-field SPL spectrum in the room (a spectrum row) — optional | dB | see below |
Worked example
Rectangular duct 315×210 mm → Ad = 0.0662 m², 10·log₁₀(Ad) = −11.79 dB. Direct-only path:
| Band (Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 |
|---|---|---|---|---|---|---|---|
| Lp,direct (dB) | 65 | 62 | 58 | 55 | 50 | 45 | 40 |
| Lw (dB) | 53.21 | 50.21 | 46.21 | 43.21 | 38.21 | 33.21 | 28.21 |
Adding a reverberant-field row at the same time raises each band slightly further, by the logarithmic sum of the two paths' individual Lw values at that band.
Source
CIBSE Guide B4 (2016), Formulas 4.29 and 4.30 — sound power entering a duct opening from a room's direct and reverberant sound fields.