Skip to content
ContentsFormula ReferenceUser guide
Formula Reference

Circular Duct Breakout

Formula
Lw,out = Lw,in − TL + 10·log₁₀(4L) − 10·log₁₀(D) (CIBSE Guide B4 Formula 4.11, Table 4.31)
Output
dB — sound power level radiated by the duct walls (Lw) per band
Bands
63 Hz – 8 kHz
Standard / Source
CIBSE Guide B4
Access
Toolbar block

What it does

Estimates the sound power that breaks out through the wall of a circular sheet-steel duct as it passes through a room or ceiling void, per CIBSE Guide B4 Formula 4.11. Takes the in-duct sound power where the duct enters that area, the steel thickness, the duct diameter and the exposed length.

Equation

Lw,out=Lw,in−TL+10log⁡10(4L)−10log⁡10(D)L_{w,\text{out}} = L_{w,\text{in}} - TL + 10\log_{10}(4L) - 10\log_{10}(D)
  • TL — breakout transmission loss of a circular duct from CIBSE Table 4.31, by steel thickness and diameter.
  • L — exposed duct length in metres; D — duct diameter in metres (you enter it in mm, as Table 4.31 lists it).

ℹ️ Table lookup. Table 4.31 lists five diameters (100, 200, 300, 600 and 1500 mm). Timbral uses the closest one; a diameter exactly halfway between two takes the lower TL band by band (the conservative choice, more breakout), and a duct outside 100–1500 mm takes the end row. No additional-length correction is applied, so a long, thin duct with a low TL can give an Lw,out above Lw,in; Timbral does not cap it.

Inputs

InputMeaningUnitExample
Lw,inin-duct sound power where the duct enters the area (a spectrum row)dBsee below
Steel duct thickness0.7 (22 swg), 0.9 (20 swg), 1.2 (18 swg) or 1.5 (16 swg)mm0.7 (22 swg)
Dduct diameter (must be greater than 0)mm315
Lexposed duct length (must be greater than 0)m5

Worked example

0.7 mm (22 swg) steel, D = 315 mm (closest Table 4.31 row: 300 mm), L = 5 m. Geometry term: 10·log₁₀(4 × 5) − 10·log₁₀(0.315) = 13.01 + 5.02 = 18.03 dB.

Band (Hz)631252505001000200040008000
Lw,in (dB)8078747065605550
TL (dB)4439342928333841
Lw,out (dB)54.057.058.059.055.045.035.027.0

(e.g. at 63 Hz: 80 − 44 + 18.03 = 54.0 dB.)

Source

CIBSE Guide B4 (2016) — Formula 4.11 (breakout from circular ducts) and Table 4.31 (breakout transmission loss of circular ducts). Bands 63–8000 Hz; Table 4.31 has no 31.5 Hz column.

Register interest

Tell us a little about you and we'll be in touch when Timbral is ready.