- Formula
- Lw,out = Lw,in − TL + 10·log₁₀(4L) − 10·log₁₀(D) (CIBSE Guide B4 Formula 4.11, Table 4.31)
- Output
- dB — sound power level radiated by the duct walls (Lw) per band
- Bands
- 63 Hz – 8 kHz
- Standard / Source
- CIBSE Guide B4
- Access
- Toolbar block
What it does
Estimates the sound power that breaks out through the wall of a circular sheet-steel duct as it passes through a room or ceiling void, per CIBSE Guide B4 Formula 4.11. Takes the in-duct sound power where the duct enters that area, the steel thickness, the duct diameter and the exposed length.
Equation
- TL — breakout transmission loss of a circular duct from CIBSE Table 4.31, by steel thickness and diameter.
- L — exposed duct length in metres; D — duct diameter in metres (you enter it in mm, as Table 4.31 lists it).
ℹ️ Table lookup. Table 4.31 lists five diameters (100, 200, 300, 600 and 1500 mm). Timbral uses the closest one; a diameter exactly halfway between two takes the lower TL band by band (the conservative choice, more breakout), and a duct outside 100–1500 mm takes the end row. No additional-length correction is applied, so a long, thin duct with a low TL can give an Lw,out above Lw,in; Timbral does not cap it.
Inputs
| Input | Meaning | Unit | Example |
|---|---|---|---|
| Lw,in | in-duct sound power where the duct enters the area (a spectrum row) | dB | see below |
| Steel duct thickness | 0.7 (22 swg), 0.9 (20 swg), 1.2 (18 swg) or 1.5 (16 swg) | mm | 0.7 (22 swg) |
| D | duct diameter (must be greater than 0) | mm | 315 |
| L | exposed duct length (must be greater than 0) | m | 5 |
Worked example
0.7 mm (22 swg) steel, D = 315 mm (closest Table 4.31 row: 300 mm), L = 5 m. Geometry term: 10·log₁₀(4 × 5) − 10·log₁₀(0.315) = 13.01 + 5.02 = 18.03 dB.
| Band (Hz) | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 |
|---|---|---|---|---|---|---|---|---|
| Lw,in (dB) | 80 | 78 | 74 | 70 | 65 | 60 | 55 | 50 |
| TL (dB) | 44 | 39 | 34 | 29 | 28 | 33 | 38 | 41 |
| Lw,out (dB) | 54.0 | 57.0 | 58.0 | 59.0 | 55.0 | 45.0 | 35.0 | 27.0 |
(e.g. at 63 Hz: 80 − 44 + 18.03 = 54.0 dB.)
Source
CIBSE Guide B4 (2016) — Formula 4.11 (breakout from circular ducts) and Table 4.31 (breakout transmission loss of circular ducts). Bands 63–8000 Hz; Table 4.31 has no 31.5 Hz column.