L_room = Lw − EnvAdj(band) − AreaAdj(S, band) − CeilingAtten(type, band)
Output
dB — room SPL from plenum breakout, per band
Bands
63 Hz – 4 kHz
Standard / Source
ASHRAE 2023
Access
Toolbar block

What it does

Predicts the sound pressure level radiated into a room from a return-air plenum above a suspended ceiling — sound that breaks out of ductwork or diffusers into the plenum, then transmits down through the ceiling tiles into the occupied space below. Combines the plenum's radiated sound power with an environmental adjustment, a source-area adjustment, and the chosen ceiling type's own sound attenuation.

Equation

Lroom=Lw−EnvAdj(band)−AreaAdj(S,band)−CeilingAtten(type, band)L_{room} = L_w - \text{EnvAdj(band)} - \text{AreaAdj}(S,\text{band}) - \text{CeilingAtten(type, band)}

EnvAdj is a fixed per-band environmental adjustment (4, 2, 1 dB at 63/125/250 Hz, 0 dB above); CeilingAtten is read from tabulated per-band data for the selected ceiling construction; AreaAdj is a small correction for the source's radiating area (non-zero only at 63/125/250 Hz, from ASHRAE Table 42; a source area exactly on a row boundary takes the later row).

Inputs

InputMeaningUnitExample
Lwplenum-radiated sound power (a spectrum row)dBsee below
Ssource aream²1.3
Ceiling typeconstruction (select, from ASHRAE table)—16mm mineral fibre 2.4 kg/m²

Worked example

S = 1.3 m², ceiling = 16mm mineral fibre 2.4 kg/m²:

Band (Hz)63125250500100020004000
Lw (dB)70686562585450
L_room (dB)51494643332417

(e.g. at 63 Hz: 70 − 4 (env) − 2 (area) − 13 (ceiling) = 51 dB.)

Source

ASHRAE, 2023 ASHRAE Handbook — HVAC Applications, Chapter 49 (Sound and Vibration Control), p49.39 — plenum breakout through a suspended ceiling.